Monitoring Templates

Priority 2 · Reusable metric libraries per device type

12
MC

Template library

TemplateDevice typeMetricsAssignedPollSource
Cisco IOS Switch
switch143830slibrary
HPE Aruba Switch
switch122130slibrary
APC Smart-UPS
ups91760slibrary
APC Rack PDU
pdu72460slibrary
Schneider EPM
sensor611120scustom · Power On Australia
HPE iLO Server
server111960slibrary
Fortinet FortiGate
firewall10830slibrary

Polling schedule

  • 30sSwitches, firewalls, routers
    high churn metrics
  • 60sServers, UPS, PDU
    balance of fidelity and load
  • 120sEnvironmental sensors
    low rate of change
  • 5mCapacity & inventory
    config, firmware, asset

Cisco IOS Switch · metric definitions

MetricOIDTypeDescriptionThresholds
cpu.5m1.3.6.1.4.1.9.9.109.1.1.1.1.8Gauge5m avg CPU70% warn · 90% crit
mem.used1.3.6.1.4.1.9.9.48.1.1.1.5GaugeMemory used %85% warn · 95% crit
if.errors1.3.6.1.2.1.2.2.1.14CounterInterface in errorsrate > 10/min warn
icmp.reachSyntheticICMP echo3 missed crit
env.temp.inlet1.3.6.1.4.1.9.9.13.1.3.1.3GaugeInlet temperature °C45 warn · 55 crit
psu.state1.3.6.1.4.1.9.9.13.1.5.1.3EnumPower supply stateany != normal crit